Brand Name : BRITEC
Model Number : TY-40R 3P
Certification : CE
Place of Origin : China
MOQ : 200 piece / pieces
Payment Terms : T/T
Supply Ability : 50000 pieces per month
Delivery Time : 15-30 days after payment
Packaging Details : EXPORT PACKING
Test standards : IEC 61643-11 / EN61643-11
Uc : 150V / 275V / 320V / 385V / 440V
In : 20kA
Imax : 40kA
Material : Thermal plastic UL94-V0
tA : ≤25ns
Mounting on : 35mm Din rail
Tu : -40℃...+80℃
Class : Type 2
System : Three phase
Type 2 Three Phase 40kA 320V Lighting Protection 3 Poles Class II Surge Arrester
Type 2 Three Phase 3 Poles Class II Surge Arrester Feature:
• TY-40R 3P is the Type 2/Class II devices for discharging voltage surges.
Type 2 Three Phase 3 Poles Class II Surge Arrester Product Details:
TY150 40R 3P | TY275 40R 3P | TY320 40R 3P | TY385 40R 3P | TY440 40R 3P | |
SPD classification according to EN61643-11 | Type 2 | Type 2 | Type 2 | Type 2 | Type 2 |
SPD classification according to IEC61643-11 | Class II | Class II | Class II | Class II | Class II |
Max. continuous operating a.c. voltage Uc | 150V | 275V | 320V | 385V | 440V |
Nominal discharge current (8/20us) In | 20kA | 20kA | 20kA | 20kA | 20kA |
Max. discharge current(8/20μs) Imax | 40kA | 40kA | 40kA | 40kA | 40kA |
Voltage protection level Up | ≤0.8kV | ≤1.3kV | ≤1.5kV | ≤1.8kV | ≤2.0kV |
Voltage protection level 5kA Up | ≤0.6kV | ≤1kV | ≤1.2kV | ≤1.4kV | ≤1.6kV |
Max. backup fuse | 125A gG | 125A gG | 125A gG | 125A gG | 125A gG |
Response time tA | ≤25ns | ≤25ns | ≤25ns | ≤25ns | ≤25ns |
Operating temperature range Tu | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ | -40℃-80℃ |
Operating state / fault indication | green / red | green / red | green / red | green / red | green / red |
Cross-section area (Min.) | 4mm2 | 4mm2 | 4mm2 | 4mm2 | 4mm2 |
Cross-section area (Max.) | 35mm2 | 35mm2 | 35mm2 | 35mm2 | 35mm2 |
For mounting on | 35mm Din rail | ||||
Enclosure material | Thermal plastic UL94-V0 | ||||
Degree of protection | IP20 | IP20 | IP20 | IP20 | IP20 |
Dimension:
Type 2 Three Phase 3 Poles Class II Surge Arrester Application:
• Suitable for the second stage of protection in supply distribution panels in which Type 1 protection devices are installed upstream, or for the first stage of protection in commercial or other applications not exposed to direct strikes and with no external lightning protection system.
Type 2 Three Phase 3 Poles Class II Surge Arrester Advantage:
• Easy replacement of protection modules without tools.
Our Services:
Test:
Certificate:
Installation:
Type 2 Three Phase 3 Poles Class II Surge Arrester 40kA 320V Lighting Protection Images |